A site standard requires an outdoor dike to hold 110% of the largest tank, which holds 12,000 gal. The dike floor is 30 ft × 40 ft, and 1 ft3 = 7.48 gal. Ignoring the volume displaced by the tanks, what minimum wall height is needed?
-
1.10 ft
Why A is wrong. 1.10 ft divides 13,200 gal by 10 instead of 7.48 gal per cubic foot, a rounding shortcut that undersizes the wall.
-
1.34 ft
Why B is wrong. 1.34 ft sizes the dike for the 12,000-gal tank alone (12,000 ÷ 7.48 ÷ 1,200) and leaves out the 10% margin the site standard requires.
-
1.47 ft
Why C is right. The required volume is 12,000 × 1.10 = 13,200 gal, or 1,765 ft3 at 7.48 gal per cubic foot; spread over the 1,200 ft2 floor, that is 1.47 ft.
Required volume 12,000 gal × 1.10 = 13,200 galVolume in cubic feet 13,200 ÷ 7.48 = 1,765 ft3Dike floor area 30 ft × 40 ft = 1,200 ft2Minimum wall height 1,765 ÷ 1,200 = 1.47 ftAnswer 1.47 ft -
11.00 ft
Why D is wrong. 11.00 ft divides 13,200 gallons straight by 1,200 ft2 and skips the conversion to cubic feet, which makes the wall 7.48 times too tall.